Power Supply
Single phase 105-130 VAC @ 15A max (or 210-250 VAC @8A max when ordered with option 15), factory set, 47-63 Hz
3-phase wye voltage:
- 0-150V rms phase-neutral, direct coupled
- 85 VA (1.13A) per phase maximum @ 75V phase-neutral output, P.F.=1.0
- 120 VA per phase maximum @ 150V phase-neutral output, P.F.=1
Single phase current:
- Switched to 3 phase output terminals, direct coupled
- 0-30A rms, 400 VA maximum, 44V rms maximum
Additional current modes:
- For simultaneous 3-phase current, MTS-1720 required
- 0-6A DC mode
- Two mixed harmonic current modes for harmonic restraint testing:
- Sum of fundamental frequency current and pure second harmonic current
- Sum of fundamental frequency current and half-wave rectified fundamental DC current
- High AC current 0-75A @3V mode for instantaneous tests (7.5 maximum compliance voltage)
- Parallel current mode allows paralleling of current outputs of MTS-1710 & MTS-1720 for up to 90amps max, 1000VA max, 44Vrms max
- Dual AC current mode for slope tests (I1: 60A maximum, 50A @3.5V, I2: see single phase current)
Note: For all current outputs, maximum obtainable current will vary inversely with load impedance.
Output frequency:
- Power line (frequency and phase locked)
- 2nd through 10th harmonic of power line
- Variable
- 40.00 - 80.00 Hz (0.001 Hz resolution, 0.01% accuracy)
- 80 - 800 Hz (0.01 Hz resolution, 0.02% accuracy)
- 25 Hz frequency mode
Four output level settings:
- Off, prefault, fault, postfault
Phase control:
- Phase between current and any voltage is adjustable from 0 through 360 degrees
- Adjustment resolution: 0.25 degrees
Start/Stop trigger inputs:
- For externally triggering fault initiation/termination
- NC or NO wet/dry contact sensing
- DC/AC voltage sensing (10V threshold level, 52k ohms input impedance minimum)
AC Voltage measurements:
- A-N, B-N, C-N, A-B, B-C, C-A
- True RMS responding, autoranging
- Voltage scales (approx):0-82V, 82-327V
- Accuracy: +/-0.5% of reading +/-0.2% of scale
AC Current measurements:
- Measures actual output current
- True RMS responding, autoranging
- Current scales (approx): 0-8.2A, 8.2-32.7A
- High current scales (approx): 0-24.5A, 24.5-98.3A
- Accuracy: +/-0.5% of reading +/-0.2% of scale
DC Current measurement:
- 0 - 10.00A scale
- Accuracy: +/-1% of reading +/-0.2% of scale
Phase measurement:
- Accuracy: +/-0.5 degrees
- 0-359.9 deg. or 0 - +/-180 deg. display modes
- Selectable V-leads-I or I-leads-V measurement reference
Time measurement:
- Measures interval from either fault initiation or external start trigger signal
- 0 - 99999 sec, autoranging scale
- 0 - 99999 cycles, autoranging scale
- Best resolution: 0.1 ms/ 0.1 cycles
- Two-wire pulse timing mode
- Accuracy: 0 - 9.9999 sec scale: +/-0.5ms +/- 1LS digit, all other scales: +/-0.005% +/-1 digit
Frequency measurement:
- Power line frequency measurement (accuracy & resolution: 0.01 Hz)
- Variable frequency value displayed to 0.001 Hz resolution
Computed measurements |
- Impedance (V/I, V/2I , V/SQRT(3)I, V/(1+kI) ) with programmable k-factor
- Resistance (Re[V/I], Re[V/2I] , Re[V/SQRT(3)I], Re[V/(1+kI)] ) with programmable k-factor
- Reactance (Im[V/I], Im[V/2I] , Im[V/SQRT(3)I], Im[V/(1+kI)]) with programmable k-factor
- Single phase power (Watts, Vars, VA, PF)
- I1/I2, I2/I1, ABS(I1-I2)/((I1+I2)/2) & I2/((2 I1+I2)/2) with programmable CT tap values for I1, I2
- Volts-per-Hz
- Breaker advance time, breaker closing angle
|
Static/Dynamic Testing capabilities |
- Phase to ground faults
- Phase to phase faults
- Three phase faults
- Two phase to ground faults
- Phase, frequency, voltage and current stepping
- Phase, frequency, voltage and current ramping with adjustable rate of change.
- Presettable fault durations, 0 - 99.9999 sec
- Programmable auto-reclose time delay and reclose-into-fault events
- Programmable breaker time
- Three-pole and single-pole tripping
- Programmable PT location simulation
- Programmable fault incidence angle (point-on-wave)
- Remote end trip simulation (with MTS-1720)
|
Fault Playback |
- Ability to accept fault data from fault recorders (in COMTRADE format), EMTP simulation outputs, or user defined waveforms
- Sample rate: Programmable 2 - 30 kHz
- Record length:
- 60000 samples per each of 4 channels
- (6 channels available when MTS-1720 is also used)
- Resolution:
- 14 bit mode: 14 bit dynamic + 16 bit scaling
- 8 bit mode: 8 bit dynamic + 12 bit scaling
- Peak output levels: +/-230.5V for voltage channels, +/-35.35A for current channels
|
RS-232C Interface |
- Two ports, optically isolated
- All instrument functions are RS-232C controllable via COM1
- COM2 auxiliary port connects to relay or device under test
- Standard baud rates from 300 to 38400 baud
- XON/XOFF handshaking protocol
- Easy-to-use terminal mode
|
Phsyical Characteristics |
- 19"W x 7.5"H x 18"D (48.3cm W x 19.1cm H x 45.7cm D)
- Weight:
- 62.0 lbs (28.2 kg) without front/rear protective covers
- 65.4 lbs (29.7 kg) with front/rear protective covers
- Built-in carry handle/tilt stand
|
Additional Standard Features |
- Synchronizing mode for testing synchronizing devices
- Internal clock/calendar
- Audible feedback tone
- Two programmable auxiliary contact outputs (5A/250 VAC, 0.5A/250 VDC) for slaving other devices
- Circuit breaker-advance time measurement
- High speed measurement modes
- Breaker signal (52A/52B) simulation
- Permissive/unblock signal simulation (with programmable delay)
- Multi-system synchronization
- User settable default output voltages and frequency
|
Options |
- Option 03*: Programmable digital I/O and trigger channels
- Option 04: Low level input to power amplifiers for advanced fault playback external phase/frequency sync input
- Option 07*: Auxiliary DC voltage output 12- 300 VDC @ 100VA maximum output to supply auxiliary power to device(s) under test.
- Option 10*: Hard-shell shipping case with casters
- Option 11: Cordura carry case
- Option 12: French display
- Option 14: 19" Rackmount enclosure
- Option 15: 240V, 50/60 Hz line input
- Option 16: Default 110V/50 Hz output
- Option 18: Foot Switch - for enabling the fault state when performing steady state testing
- Option 19: Additional Operation and Reference Manual
- Option 20: 1 Year extended warranty
- Option 21 :Test lead kit for AC voltage, AC current, DC voltage, & contact sense
- Full-Service Agreement Preventative maintenance, calibration and service plan
- CABLE C1 MTS-1710 to SEL-121 communication cable
- CABLE C2 MTS-1710 to SEL-221, SEL-251, and SEL-321 relay communication cable
- CABLE C3 MTS-1710 to GEC Optimho relay communication cable
- 12-3415-00 LED Photo Sensor Cable - for sensing operation of LED targets
- 12-3339-00 MTS-1710 COM2 Adapter Cable - Adapter cable for communicating to relay from COM 2 using a cable from the manufacturer intended to connect to computer serial port.
- 12-2539-00 MTS-1710 to MTS-1710 Synchronization cable
- MTS-1720 Two Channel Current Source (Integrates to build a full 3-phase voltage, 3-phase current system)
- MTS-1730 Digital Input/Output Signal Conditioner
- MTS-1750 High Current Source
- MTS-1753 Three Channel High Current Source
* Included free with all new orders
Download full