- Ten simultaneous measurements
- Very responsive controls and displays
- Lightweight, easy to use
- High ampacity current inputs
- True RMS, fully autoranging
- Phasor display of AC quantities
- Optimized for relay and meter applications
- High intensity LED displays
- Battery or AC powered
|
|
|
| Power Supply |
- 120 VAC/60 Hz version: 100-130VAC at 50-70Hz
- 240 VAC/50/50 Hz version: 220-260VAC at 47-70Hz
- Internal 12VDC battery pack for 7 hour operation
|
| Frequency measurement |
- Ranges: 8.00 - 99.99Hz (low scale), 8.0-500.0 Hz (high
scale)
- Resolution:
- 0.001 Hz for 8.000-9.999 Hz input
- 0.01 Hz for 10.00-99.99 Hz input
- 0.1 Hz for 100.0-650.0Hz input
- Accuracy: +/-0.01 Hz (low scale), +/- 0.1 Hz (high scale)
- Measurement speed:
- Measurement speed is dependent upon input frequency
- for 60 Hz input: 2 readings/sec (normal mode), 7.5
readings/sec (high speed mode)
- for 50 Hz input: 1.6 readings/sec (normal mode), 6.3
readings/sec (high speed mode)
|
|
Time (seconds) measurement
|
- Range: 0.0ms - 9999 sec, autoranging at the end of each
decade
- Resolution: 0.1ms (lowest scale)
- Accuracy: +/-0.5 ms (0-10 seconds), +/-0.01% (10-9999
seconds)
|
|
Time (cycles) measurement
|
- Range: 0.0 - 9999 cycles, autoranging at 999.9 cycles
- Resolution: 0.1cycles (lowest scale)
- Accuracy: +/-0.1cycles (lowest scale)
|
|
Phase measurement
|
- Ranges: 0.0 to 360.0 degrees or +/-180.0
- Resolution: 0.01 degree for readings from -9.99deg to
10.00 degrees, 0.1 degree otherwise
- Accuracy: +/-0.5 deg. down to 2V/200mA
- Measurement speed:
- Measurement speed is dependent upon input frequency
- for 60 Hz input: 2 readings/sec (normal mode), 7.5
readings/sec (high speed mode)
- for 50 Hz input: 1.6 readings/sec (normal mode), 6.3
readings/sec (high speed mode)
|
|
AC/DC Voltage measurement
|
- True RMS responding, DC coupled
- Measures any combination of phase-to-ground or phase-phase
voltage selected by front panel color coded pushbuttons
- Accuracy: +/-0.4% of reading +/- 0.15% of scale
- Ranges: 0-19.99/ 199.9/ 1999V, autoranging at 19.99, 199.9V
- Maximum input: 600VAC continuous
- Resolution: 0.01V (lowest scale)
- Input impedance: 2 megohms
- Measurement speed: 3 readings/sec (normal mode), 30 readings/sec
(high speed mode)
|
|
AC Current measurement
|
- True RMS responding, AC coupled
- Measures any combination of phase-to-ground or phase-phase
vector selected by front panel pushbuttons
- Accuracy: +/-0.4% of reading +/- 0.15% of scale
- Ranges: 0-1.999/ 19.99/ 199.9A, autoranging at 1.999,
19,99A
- Maximum input: 75A continuous, 125A for 5 seconds
- Resolution: 0.001A (lowest scale)
- Measurement speed: 3 readings/sec (normal mode), 30 readings/sec
(high speed mode)
|
|
Power measurement
Power measurements are calculated by the internal microprocessor
from the current, voltage and phase angle measurements.
|
Kilowatts |
- Resolution: up to 0.001kWatt
- Accuracy: 0.8% at P.F.=1
- Range: -63.0 to +63.0 kW
|
|
Kilovars
|
- Resolution: up to 0.001kVAR
- Accuracy: 0.8% at P.F.=0
- Range: -63.0 to +63.0 kVAR
|
|
Kilovoltamperes
|
- Resolution: up to 0.001kVA
- Accuracy: 0.8%
- Range: -63.0 to +63.0 kVA
|
|
Power Factor
|
- Resolution: up to 0.001
- Accuracy: +/- 0.004 for sinusoidal inputs
- Range: -1.000 to +1.000
|
|
External Trigger
|
- Floating three-terminal inputs for start and stop triggers
- Change of state detection for contact or AC/DC voltage
(30-300V)
- Contact inputs protected to 300V AC/DC
- Input impedance: 60kohm minimum
- Selectable audio tone for continuity indication of stop
trigger
- Start trigger starts timer, increases update frequency
of voltage, current, phase and frequency readings
- Stop trigger stops timer and freezes all measurement readings
|
|
RS-232C Interface
|
- Data format: 8 bits, no parity, 1 start bit, 1 stop bit
- Speed: Standard baud rates from 1100 to 9600 baud
- Connector: Standard 25-pin female DB-25, DCE configuration
- Permits control of all meter functions for fully automated
or semi-automated testing
- Permits automated output and recording of all measurements
|
|
Phsyical Characteristics
|
- Aluminum case and frame
- Moulded ABS plastic front/rear covers
- Integrated carry handle/tilt stand
- Large rear feet allow vertical operation
- Dimensions: 14"W x 6"H x 10.5"D (35.56cm
W x 15.36cm H x 26.88cm D)
- Weight: 15.8 lbs/7.2kg (22.2lbs/10.1kg including battery)
|
|
Options
|
- Option 01: Cordura carry case
- Option 02: Snap-on lead case
- Option 03: Impedance measurement
- Option 06: IEEE-488 Interface
- Option 08: W, VAR, VA display
- Option 09: Ratio measurement
- Option 10: Slip frequency
- Option 14: Synchrocheck
- Option 17: Signal processing
Adds 3 additional measurement capabilities:
- Low pass filter for channel 1
- Average responding AC measurement on channel 1
- Peak hold peak responding measurement for channels
1& 2
- Option 18: Extended low level phase measurement
- Option 20: Hard-shell shipping case
- Option 21: 10V Triggers
- Option 22: 0-20amp input
- Option 23: 240V, 50Hz nominal AC line
voltage input
- Option 24: Extra manual
- Option 25: 1 Year extended warranty.
Additional year for a total of 2 years
- Full-Service Agreement Preventative
maintenance, calibration and service plan
Download
full MTS-1030 Series brochure 165kB
PDF format |
NOTE: All specifications are subject
to change
|